Visual Circuits MZ Uživatelský manuál Strana 4

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 4
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 3
Page 4 of 4 — DN-6859:A • 10/10/06
NOTIFIER® and ONYX® is a registered trademark of Honeywell
International Inc.
©2006 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
FOR ICM-4RK AND ICE-4:
Maximum current per module is 6.0 amps.
Maximum current per circuit is 3.0 amps.
End-of-line device is a 4.7 K ohm, 1/2 Watt resistor, for
Class B configuration.
Current draw: For ICM-4RK, 0.007 A in standby, 0.072 A in
alarm. For ICE-4, 0.001 A in standby, 0.065 A in alarm.
Note: Each ICM-4RK or ICE-4 may be powered from two sep-
arate power supplies. Use one main power supply plus one
APS-6R, or use two APS-6Rs to provide a total alarm current
per module or expander of 6.0 amps with a maximum current
per circuit of 3.0 amps.
FOR IZM-8RK AND IZE-A:
Loop voltage (standby): 17 – 26.5 VDC.
Ripple: 100 mV maximum.
Detector standby current: 2.5 maximum.
Loop resistance: 100 ohm maximum.
Alarm impedance: 400 ohm minimum to 1150 ohm maxi-
mum.
Minimum voltage with minimum alarm impedance: 10 VDC.
Maximum alarm current available: 45 mA.
End-of-line device is a 4.7 K ohm, 1/2 Watt resistor, for
Class B configuration. Note: IZM-8 with IZE-A does not
require an EOL device.
Current draw: For IZM-8RK, 0.047 A in standby, 0.047 A in
alarm. For IZE-A, 0.004 A in standby, 0.047 A in alarm.
FOR VCM-4RK AND VCE-4:
Up to 30 watts per circuit or 120 watts per VCM-4RK or
VCE-4.
Up to seven telephones on the telephone circuit (on any cir-
cuit).
25 or 70.7 Vrms speakers.
End-of-line device is a 4.7 K ohm, 1/2 watt resistor, for
Class B configuration for 25 V; or 4.7 K ohm, 2 watts for
70.7 V.
Select switches by circuit with soft-feel, rubber tactile key-
pad.
Current draw: For VCM-4RK, 0.007 A in standby, 0.040 A in
alarm. For VCE-4, 0.001 A in standby, 0.040 A in alarm.
FOR DCM-4RK
Four dual-channel circuits (expansion to eight circuits not
permitted).
25 or 70.7 Vrms speakers.
End-of-line device is a 4.7 K ohm, 1/2 watt resistor, for
Class B configuration; 4.7 K ohm, 2 watts for 70.7 Vrms.
Select switches by circuit with soft-feel, rubber tactile key-
pad.
Current draw: 0.008 A in standby, 0.080 A in alarm.
Product Line Information
CRM-4RK Control Relay Module, rubber keypad.
CRE-4 Control Relay Expander.
ARM-4 Auxiliary Relay Module.
ICM-4RK Notification Appliance Circuit Module,
rubber keypad.
ICE-4 Notification Appliance Circuit Expander.
IZM-8RK Initiating Zone (Initiating Device Circuit)
Module (NFS-3030 only).
IZE-A Initiating Zone Expander; allows Class A/
B selection for IZM-8RK (NFS-3030
only).
VCM-4RK Four-circuit Voice Control Module, rubber
keypad. Selected as either a speaker or
telephone module.
VCE-4 Voice Control Expander. Expands the
VCM-4 to eight circuits.
DCM-4RK Dual Channel Module, rubber keypad.
CHS-4MB Expansion Chassis. Mounts up to four
modules. Includes CHS-4N, MP-1B
(Module Dress Panel), and Expander
Ribbon Cable.